Technical data
SHGZ7/1620-4 L R22
Application | Refrigeration & AC |
Compressor refrigeration capacity | 11.70 kW |
Power consumption | 15.90 kW 1) |
Current draw (400 V) | 32.20 A |
Mass flow | 0.057 kg/s |
at following operating condition:
Refrigerant | R22 |
Reference temperature | Dew point |
Evaporating temperature | -50.0 °C |
Condensing temperature | 37.4 °C |
Air inlet temperature | 32.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas superheat | 10 K |
Subcooling (outside cond.) | -- K |
Number of cylinders / Bore / Stroke | 6 / 70 mm / 70 mm |
Displacement LP/HP 50 Hz (1450 ¹/min) 2) | 93,70 / 46,90 m³/h |
Voltage 3) | 380-420V Y/YY -3- 50Hz PW |
Winding divided into | 50% / 50% |
Max. working current 4) | 50.0 A |
Max. power consumption 4) | 27.0 kW |
Starting current (rotor blocked) 4) | 175.0 / 269.0 A |
Motor protection | MP10 |
Protection terminal box | IP 65 |
Weight | 489 kg |
Max. permissible pressure (LP/MP/HP) 2) | 19 / 19 / 28 bar |
Connection suction line SV | 54 mm - 2 1/8 " |
Connection liqiud outlet line FLA | 22 mm - 7/8 " |
Lubrication | Oil pump |
Oil type R404A, R410A, R448A/R449A | FUCHS Reniso Triton SE 55 |
Oil type R22 | FUCHS Reniso SP 46 |
Oil charge | 4,5 Ltr. |
Oil sump heater | 230 V - 1 - 50 Hz, 140 W |
Dimensions
Length / Width / Height | 1300 / 1090 / 1610 mm |
Number fan motors | 4 |
Voltage | 230 V - 1 - 50 Hz |
Max. working current 50 Hz | 4 x 3,00 A |
Max. power consumption 50 Hz | 4 x 680 W |
Air flow 50 Hz | 21210 m³/h |
Receiver content | 35.00 Ltr. |
R404A / R507 5) | 33,6 / 33,7 kg |
R22 5) | 38,1 kg |
Scope of supply
Semi-hermetic motor compressor HGZ(X) (Extent of
delivery see compressor) installed with rubber anti-vibration pads on liquide
receiver. The liquid receivers with sight glass and Rotalock shut-off valve with
brazing connection. Tank is provided (appropriate pressure appliance guideline)
Oil pump
Air-cooled finned tube condenser with 4
ventilators:
- Ventilators 230 V - 1 - 50/60 Hz, with bimetal winding
protection, phase control for speed adjustment (regulator not included in scope
of supplies)
- With piping on discharge and liquide side. Service charge
4 rubber plates enclosed for installation of the condensing unit
Accessories
Oil sump heater 230 V - 1 - 50/60 Hz, 140 W
Oil pressure safety switch MP54 230 V - 1 - 50/60 Hz,
IP20
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz
Oil service valve
Thermal protection thermostat per cylinder cover
6)
High pressure safety limiter + controller/ +low pressure
controller 6)
Safety valve for receiver 6)
Oil separator incl. mounting
Ventilators 230 V D / 400 V Y - 3 - 50/60 Hz
Special voltage and/or frequency (on request)
Notes
1) | Power consumption of condenser fans included.
|
2) | LP = Low
pressure MP = Middle pressure HP = High pressure |
3) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
4) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing fuses, supply lines and
safety devices. Fuse: Consumption category AC3. |
5) | With liquide temperature at 20°C and 90 % capacity |
6) | Mounted |