Technical data
HGX66e/1750 ML 44 LG
Application | Refrigeration & AC |
Compressor refrigeration capacity | 83.60 kW |
Power consumption | 25.20 kW |
Current draw (400 V) | 47.80 A |
Mass flow | 0.585 kg/s |
at following operating condition:
Refrigerant | R134a |
Reference temperature | Dew point |
Evaporating temperature | 5.0 °C |
Condensing temperature | 50.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 6 / 80 mm / 58 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 152,2 / 182,6 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 50% / 50% |
Max. working current 2) | 71.9 A |
Max. power consumption 2) | 42.4 kW |
Starting current (rotor blocked) 2) | 196.0 / 335.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 280 kg |
Max. permissible pressure (LP/HP) 3) | 19 / 28 bar |
Connection suction line SV | 54 mm - 2 1/8 " |
Connection discharge line DV | 42 mm - 1 5/8 " |
Lubrication | Oil pump |
Oil type R134a, R404A, R407A/C/F, R448A, R449A, R450A, R513A | FUCHS Reniso Triton SE 55 |
Oil type R1234yf, R1234ze, R455A, R454C | FUCHS Reniso Triton SE 55; to>15 °C: GEA Bock C 85 E |
Oil charge | 4,4 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 160 W |
Dimensions
Length / Width / Height | 810 / 557 / 467 mm |
Sound power level LWA 4) | 88 db(A) @ -35 °C / +40 °C |
| 83 db(A) @ -10 °C / +45 °C |
Sound pressure level LpA 4) | 75 db(A) @ -35 °C / +40 °C |
| 70 db(A) @ -10 °C / +45 °C |
Scope of supply
Semi-hermetic six-cylinder reciprocating compressor with
drive motor for part winding start
Single-section compressor housing with
hermetically integrated electric motor
Oil pump
Winding protection with PTC resistor sensors. Electronic
triggering unit INT69 G to be fitted in switch cupboard (enclosed)
Possibility of
connection of oil level controllers ESK, AC+R or CARLY
Possibility of connection of oil level controllers Traxoil 5)
Oil charge:
FUCHS
Reniso Triton SE 55
Sight glass
Internal safety valve
Suction and discharge line valve
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet 6)
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1-2
capacity regulator = 66/33% residual capacity 7)
Compressor oil GEA Bock C 85 E (factory filling)
8)
Cylinder cover prepared for capacity regulator 9)
Oil sump heater 230 V - 1 - 50/60 Hz, 160
W 9)
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 6)
Rear bearing flange prepared for oil differential
pressure sensor DELTA-P II 9)
Oil service valve
Thermal protection thermostat per cylinder cover
9)
Connection piece suction and discharge valve in welding
design
Oil temperature sensor (Pt1000, for external evaluation)
9)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 6)
Step protection 6)
Injection nozzle 6)
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing fuses, supply lines and
safety devices. Fuse: Consumption category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the
standard rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used .
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
5) | Only with additional
adapter possible |
6) | Enclosure |
7) | Capacity regulator premounted, control unit enclosed
|
8) | from to>15°C for R1234yf/R1234ze |
9) | Mounted |