Semi-hermetic, suction gas-cooled 4-cylinder reciprocating compressor in
compact design especially for the use with hydrocarbons. The best possible
serviceability is provided by means of a replaceable drive unit, among other
things. The compressor stands out due to its outstanding running comfort and
efficient operating performance. The suction shut-off valve can be rotated by
90° in each instance. Dependable mechanism lubrication is guaranteed by means of
an oil pump which is independent of rotating direction, as well as a
large-volume oil sump. The optional oil sump heating is carried out using an
immersion sleeve and can therefore be replaced without intervening in the
refrigeration cycle.
An additional connection facility for an oil level regulator is available as
a standard. The electrical connection is simplified by means of a large-volume
electric terminal box. The electronic motor protection INT69 G (for installation
in the switch cabinet) uses PTC sensors in series to monitor the winding
temperature and optionally the discharge gas temperature. The compressor has to
be equipped with heat protection thermostat and oil sump heater. The oil
filling is the special oil Synth 68. To ensure the safety measures, an
additional agreement has to be signed.
Colour: blue (RAL 5000)
Technical data
HG44e/770-4 HC
Application | Refrigeration & AC |
Compressor refrigeration capacity | 30.00 kW |
Power consumption | 11.60 kW |
Current draw (400 V) | 20.80 A |
Mass flow | 0.102 kg/s |
at following operating condition:
Refrigerant | R290 |
Reference temperature | Dew point |
Evaporating temperature | -10.0 °C |
Condensing temperature | 45.0 °C |
Supply frequency | 50 Hz |
Voltage | 400 V |
Suction gas temperature | 20 °C |
Subcooling (outside cond.) | 0 K |
Number of cylinders / Bore / Stroke | 4 / 70 mm / 50 mm |
Displacement 50/60 Hz (1450/1740 ¹/min) | 67,00 / 80,40 m³/h |
Voltage 1) | 380-420V Y/YY -3- 50Hz PW |
| 440-480V Y/YY -3- 60Hz PW |
Winding divided into | 50% / 50% |
Max. working current 2) | 30.0 A |
Max. power consumption 2) | 17.8 kW |
Starting current (rotor blocked) 2) | 101.0 / 174.0 A |
Motor protection | INT69 G |
Protection terminal box | IP 66 |
Weight | 171 kg |
Max. permissible pressure (LP/HP) 3) | 19 / 28 bar |
Connection suction line SV | 42 mm - 1 5/8 " |
Connection discharge line DV | 28 mm - 1 1/8 " |
Lubrication | Oil pump |
Oil type R290, R600a, R1270 | FUCHS Reniso SYNTH 68 |
Oil charge | 2,7 Ltr. |
Oil sump heater | 230 V - 1 - 50/60 Hz, 160 W |
Dimensions
Length / Width / Height | 695 / 361 / 383 mm |
Sound power level LWA 4) | 80 db(A) @ -35 °C / +40 °C |
| 78 db(A) @ -10 °C / +45 °C |
Sound pressure level LpA 4) | 67 dB(A) @ -35 °C / +40 °C |
| 65 db(A) @ -10 °C / +45 °C |
Scope of supply
Semi-hermetic four-cylinder reciprocating compressor
with drive motor
Single-section compressor housing with hermetically integrated electric motor
Oil pump
Winding protection with PTC resistor sensors. Electronic
triggering unit INT69 G to be fitted in switch cupboard (enclosed)
Possibility of
connection of oil level controllers ESK, AC+R or CARLY
Possibility of connection of oil level controllers Traxoil 5)
Oil charge:
HG HC: FUCHS Reniso SYNTH 68
Sight glass
Pressure relief valve
Suction and discharge line valve
Inert gas charge
4 anti-vibration pads enclosed
Accessories
Start unloader by means of a ESS (Electronic Soft
Start), 400 V - 3 - 50/60 Hz, IP20 (Connection clamps IP00) for installation in
switch cabinet 6)
Capacity regulator 230 V - 1 - 50/60 Hz, IP65
1 capacity regulator = 50% residual capacity
Cylinder cover prepared for capacity regulator
Oil sump heater 230 V - 1 - 50/60 Hz, 160
W
Oil differential pressure sensor DELTA-P II 220-240 V -
1 - 50/60 Hz 7)
Rear bearing flange prepared for oil differential
pressure sensor DELTA-P II
Thermal protection thermostat per cylinder cover
USB converter for INT69 G Diagnose 6)
Connection piece suction and discharge valve in welding
design
Intermediate flange for discharge line valve on right or
left seen from oil pump 6)
Oil temperature sensor (Pt1000, for external evaluation)
6)
INT69 G Diagnose 115-230 V AC, 50/60 Hz, IP00 (INT69 G
not applicable)
DP-Modbus Gateway 115-230 V AC, 50/60 Hz, IP00 including
adapter cable 6)
Modbus-LAN Gateway 230 V AC, 50/60 Hz,
IP00 6)
Additional fan
230 V AC - 1 - 50 Hz, 97 W,
IP44
230 V AC - 1 - 60 Hz, 128 W 6)
Step protection
Special voltage and/or frequency (on request)
Notes
1) | Tolerance (± 10%)
relates to the mean value of the voltage range. Other voltages and current types
on request
All data are based on voltage rms values
PW = part
winding, motors for part winding starting (no start unloaders required)
Designs for Y/D on request |
2) | - The stated value for the max. power consumption is valid
for the adjusted power supply.
- Starting current (rotor blocked):
- Part winding (PW) motors: Winding 1 / Winding 1+2
- Delta/Star (Δ/Y) motors: Δ / Y
- Take account of the max.
operating current / max. power consumption for designing fuses, supply lines and
safety devices. Fuse: Consumption category AC3. |
3) | LP = Low
pressure HP = High pressure |
4) | Declared dual-number noise emission values are in
accordance with ISO 4871. The corresponding uncertainty to the sound power level
is KWA = 2,5 dB and to the sound pressure level is KpA =
2,5 dB. The values are valid for 50 Hz with the refrigerant R404A at the
standard rating points according to EN 12900.
- A-weighted sound power level LWA (re 1 pW), in decibel. To
determine the values, measurement methods of the ISO 3740 standard with
accuracy class 2 or higher were used .
- A-weighted sound pressure level LpA (re 20 µPa), in decibel.
The values are calculated from the sound power level in accordance with ISO
11203: LpA = LWA - Q2 at a distance of d = 1m
to the reference box.
|
5) | Only with additional
adapter possible |
6) | Enclosure |
7) | Enclosure (screw-in part mounted) |